← Back to standards
AS 1668.1Current

Fire and smoke control in buildings

A practical guide to HVAC systems that shut down, start, pressurize, exhaust smoke or change damper positions during fire mode — and why normal air-conditioning changes can become fire-safety modifications.

01

“We are replacing a fan, AHU or damper. How do I know whether this ordinary HVAC job also changes the building’s fire and smoke-control system?”

Many mechanical modifications are scoped around normal operating airflow only. The risk appears when the same equipment has a different role during a fire event — shutdown, smoke exhaust, stair pressurization, zone pressurization or manual fire-fan control.

02

The practical answer

Check the fire-mode role before finalizing the HVAC change. If the equipment, controls, power supply, dampers or air paths participate in smoke control or fire-mode shutdown, the modification needs a coordinated fire/smoke review.

AS 1668.1 sets minimum requirements for the design, construction, installation and commissioning of mechanical smoke-control systems. It does not decide which buildings require those systems; that is an NCC and project-approval question.

The Standard includes specific smoke-control methods and operational requirements for fans, dampers and controls. Systems not intended to operate in fire mode may still be required to shut down.

A like-for-like mechanical replacement can still create a fire-safety issue if fan performance, controls, power, damper logic, BMS interfaces or manual override arrangements change.

AS Applied rule of thumbChoose the scope, design basis and evidence pathway first. Do not start by hunting for a single clause, percentage or formula that makes the preferred answer work.
03

Where this Standard fits

Common starting points
  • Stair or fire-isolated exit pressurization
  • Smoke exhaust systems
  • Zone pressurization systems
  • AHUs and ventilation systems that change mode during fire alarm
  • Fire fan control panels and manual override functions
  • Tenancy alterations affecting ducts, dampers or compartment air paths
Do not assume
  • Every HVAC system is a smoke-control system
  • Normal airflow testing proves fire-mode performance
  • A same-size replacement fan is automatically equivalent
  • The BMS alone defines the fire matrix
  • Maintenance requirements are contained entirely in AS 1668.1
  • A tenancy change is harmless because the main plant is unchanged
04

Does the HVAC modification affect fire and smoke control?

Trace the equipment through the fire matrix and air path. The question is functional, not just whether the asset tag says ‘fire fan’.

1Recover the fire-mode basisFind the fire matrix, smoke-control drawings, damper schedule, fire fan control information and commissioning records.
2Identify every affected componentFans, AHUs, VAV terminals, motorized dampers, smoke-control dampers, sensors, controls and power interfaces.
3Define normal and fire modes separatelyState what each component does before alarm, after initiation and under manual override.
4Check changed performance and failure behaviourFan duty, damper position, control delay, loss of power and interlocks can all change the smoke-control outcome.
5Coordinate disciplinesMechanical, fire, controls, electrical and building-certification inputs should describe the same sequence.
6Commission the complete sequenceTest actual mode changes, status indication, manual controls and pressure or smoke-control performance as relevant.
The most common failure is a broken chain of assumptions.

A good result needs the equipment definition, loads, design method, fabrication, inspection and operating limits to describe the same real system.

05

Key engineering concepts to understand

01

The NCC decides where smoke control is required

AS 1668.1 provides the mechanical smoke-control requirements once the applicable building pathway has been established.

02

Normal mode and fire mode are different systems

The same fan may stop, start, reverse duty or operate with different damper positions when fire mode is initiated.

03

Controls are part of the engineering design

Automatic initiation, manual override, indication and component status need to be coordinated, not left as a generic controls contractor task.

04

Air paths matter in fire mode

Changing a duct, damper or tenancy layout can affect compartment pressure and smoke movement even when the main fan is untouched.

05

Power and wiring can be functional requirements

Equipment required to operate in fire mode may have specific power, wiring and mechanical-protection expectations.

06

Commissioning is system-level evidence

A fan factory test or individual damper test does not prove the installed smoke-control sequence works as a whole.

06

Detailed engineering case studies

The examples below show how the Standard changes a real engineering decision. They are not clause summaries or universal answers; each case starts with the equipment, task and evidence available.

Case study 1 · AHU replacement

New supply fan matches normal airflow but not the original fire-mode basis

01
Project context

A commercial building replaces an AHU fan with a modern EC fan array. Normal supply-air duty is matched and energy performance improves, but the old fan also operated as part of a zone pressurization arrangement.

Why this Standard matters

AS 1668.1 becomes central because fire-mode performance, controls and failure behaviour may differ even when normal airflow is equivalent.

What made the job difficult

  • The original fire-mode duty is only shown on old commissioning sheets.
  • The new fan array has different drive and control architecture.
  • The BMS contractor proposes reusing the old sequence without full review.
  • Existing dampers have uncertain stroke and position feedback.

How the engineering review should proceed

  1. Recover the fire-mode sequence and required system performance before final fan selection.
  2. Compare the new fan arrangement under normal, fire and failure conditions, including control and power interfaces.
  3. Verify damper operation, status indication and manual control functions that interact with the new plant.
  4. Commission the complete fire-mode sequence rather than only the fan airflow.
Practical outcome

The fan replacement becomes a fire/smoke-control modification requiring coordinated mechanical and controls verification. A normal-duty match alone is not enough.

Also investigate
Fire matrixElectrical supplyBMS/FDCIE interfacesCommissioning
Case study 2 · Tenancy fit-out

New partitions and duct branches alter a smoke-control zone

02
Project context

A large office floor is subdivided into new tenancies. Duct branches, VAV boxes and motorized dampers are relocated to suit the fit-out.

Why this Standard matters

The main AHU is unchanged, but the air paths and controls within the smoke-control zone may no longer match the original zone pressurization design.

What made the job difficult

  • The fit-out drawings focus on comfort air distribution.
  • Some existing smoke-control dampers are hidden above new ceilings.
  • VAV terminal behaviour during fire mode is not documented in the tenancy package.
  • The fire matrix has not been updated for the new layout.

How the engineering review should proceed

  1. Compare the new tenancy layout with the original smoke-control zones and compartment boundaries.
  2. Identify all affected motorized and smoke-control dampers and their fire-mode positions.
  3. Review VAV and terminal behaviour so normal controls do not prevent the required fire-mode pressure relationships.
  4. Update the fire matrix and commissioning scope before occupation.
Practical outcome

The fit-out requires a coordinated smoke-control review even though no major plant is replaced. The key deliverable is a verified final air path and control sequence for the altered floor.

Also investigate
AS 1670.1Fire compartmentationTenancy controlsAccess for inspection
Case study 3 · Existing building performance

Stair pressurization system fails field testing after years of alterations

03
Project context

A multi-storey building has recurring problems during periodic testing: some stair doors are difficult to open while upper levels do not achieve expected pressure performance.

Why this Standard matters

The issue cannot be reduced to ‘increase the fan speed’. AS 1668.1 smoke-control performance depends on leakage paths, relief, doors, controls and the complete building system.

What made the job difficult

  • Door replacements and sealing works have changed leakage over time.
  • Several tenancy refurbishments altered corridor and lobby arrangements.
  • The fan VSD settings were changed after earlier complaints.
  • The original commissioning report is incomplete.

How the engineering review should proceed

  1. Review the current building configuration and the original pressurization basis together.
  2. Measure pressure and door forces under representative fire-mode conditions and identify where the system loses or traps air.
  3. Check fan control, relief paths, doors and compartment leakage before changing capacity.
  4. Document any building changes that need correction or incorporation into a revised engineering basis.
Practical outcome

The solution may involve balancing, relief, door or leakage-path corrections rather than a larger fan. The final outcome should restore a coherent system-level basis and commissioning record.

Also investigate
Building alterationsDoor forcesFire mode controlsAS 1851 maintenance testing
07

Common mistakes

Checking only normal airflow

Equipment may have a different role, duty or control sequence during fire mode.

Treating the fire matrix as controls-only paperwork

The matrix should represent the mechanical design intent and actual component behaviour.

Assuming same kW or same airflow means equivalent

Fire-mode performance, controls, redundancy and failure behaviour may differ.

Ignoring tenancy changes

Partitions, ducts and dampers can alter smoke-control zones without changing central plant.

Commissioning components separately

The installed system needs sequence-level verification.

Using AS 1668.1 to decide whether smoke control is required

That trigger is an NCC and project-approval question.

08

Information to gather before making the decision

Building classification and NCC approval basis

Fire engineering report where applicable

Fire matrix

Smoke-control drawings and schematics

Fan and AHU schedules

Damper schedule and locations

FDCIE/FFCP/BMS interface information

Electrical supply and wiring basis

Original commissioning results

Current maintenance test records

Tenancy and building alterations

Proposed equipment or control changes

09

What should happen next?

1

Replacing plant

Confirm fire-mode duty and controls before selecting the replacement equipment.

2

Altering ducts or tenancy layout

Map the change against smoke-control zones and damper functions.

3

Field test failure

Investigate the complete air path, leakage, doors, relief and controls before simply increasing fan duty.

4

Unclear fire matrix

Reconstruct the design intent and coordinate mechanical, fire, controls and electrical disciplines.

5

Routine maintenance question

Use AS 1851 and the building’s maintenance regime; AS 1668.1 does not contain the complete maintenance pathway.

Related AS Applied content

10

Source basis & limitations

  • The page does not reproduce smoke-control operating tables, wiring tables, detailed system figures or commissioning criteria.
  • The NCC is treated as the trigger for where smoke control is required, consistent with the Standard’s own scope notes.
Project-specific engineering

Need the Standard applied to real equipment?

AS Applied helps frame the question. Detailed assessment, design, FEA, repair design, verification and RPEQ services are provided through XPO Engineers.

Ask an engineer