← Back to standards
AS 1668 seriesCurrent core parts reviewed

Ventilation and air-conditioning in buildings

A practical series guide for deciding whether the real problem is mechanical ventilation, natural ventilation, fire and smoke control, or microbial-control design and maintenance.

01

“The building has an HVAC or ventilation problem. Which part of AS 1668 should I actually be looking at?”

The phrase ‘AS 1668 compliance’ is too broad to be useful. A stale office, a naturally ventilated warehouse, an AHU that operates in fire mode and a poorly maintained cooling tower are different engineering problems and should start in different documents.

02

The practical answer

Start with the function of the system and the decision you need to make — not with the series number alone.

Use AS 1668.2 when the core question is mechanical ventilation of buildings or car parks, including outdoor air, exhaust, make-up air, contaminant control and vehicle-emission ventilation.

Use AS 1668.4 when the ventilation strategy relies on permanent natural openings and the question is whether those openings provide a valid natural-ventilation pathway.

Use AS 1668.1 when the HVAC system, fans, dampers, ducts or controls have a fire-mode or smoke-control role. Normal operating airflow does not prove that the fire-mode sequence is correct.

Use AS/NZS 3666.1 and 3666.2 where moisture, cleanliness, access, cooling water, microbial control, commissioning or ongoing maintenance is the real issue.

AS Applied rule of thumbChoose the scope, design basis and evidence pathway first. Do not start by hunting for a single clause, percentage or formula that makes the preferred answer work.
03

Where this Standard fits

Common starting points
  • Office, retail, education or hospitality ventilation questions
  • Exhaust systems for toilets, kitchens, plant rooms and other enclosures
  • Car parks and vehicle facilities
  • Warehouses and buildings relying on natural ventilation openings
  • HVAC systems that shut down, pressurize or exhaust smoke during fire mode
  • Air-handling systems where condensate, wet filters, drainage or cleanliness are concerns
Do not assume
  • A single ventilation-rate table for every building problem
  • A thermal-comfort Standard
  • Proof that high CO2 alone establishes non-compliance
  • A substitute for the NCC or project approval pathway
  • Permission to modify an AHU without checking its fire-mode role
  • A complete maintenance program without AS/NZS 3666 and other relevant service requirements
04

Which part of the AS 1668 / AS/NZS 3666 cluster should you investigate?

Define the system function first. Many existing buildings involve more than one pathway, but one question usually needs to lead the review.

Series navigator

AS 1668 series navigator

Mechanical ventilation, natural ventilation, smoke-control and hygiene questions start in different parts of the AS 1668 / AS/NZS 3666 cluster.

AS 1668 cluster — which part matches the system function Start from the system function: mechanical ventilation goes to AS 1668.2, permanent natural openings to AS 1668.4, fire and smoke control roles to AS 1668.1, hygiene and moisture questions to AS/NZS 3666. One air handler can hold several roles. What is the system function? AS 1668.2 fans, exhaust, car parks AS 1668.4 permanent natural openings AS 1668.1 fire & smoke control role AS/NZS 3666 hygiene, moisture, maintenance One air handler can hold several of these roles — document the interfaces

How to use this summary

  • Mechanical ventilation questions usually start in AS 1668.2.
  • Natural ventilation by permanent openings usually starts in AS 1668.4.
  • Fire-mode or smoke-control functions bring in AS 1668.1.
  • Cooling-tower hygiene and some contamination questions bring in AS/NZS 3666.

Real projects often touch more than one document family at once.

1What is the immediate problem?Outdoor-air adequacy, exhaust, natural openings, fire-mode operation, moisture, cleanliness or maintenance records?
2Is the ventilation mechanically driven?If fans and air-handling systems provide the ventilation, start with AS 1668.2 and define the occupancy, enclosure use and contaminant source.
3Does the design rely on natural openings?If permanent openings are the ventilation strategy, investigate AS 1668.4 and the NCC pathway rather than assuming open doors or windows are enough.
4Does any equipment operate differently in fire mode?If fans, dampers or AHUs shut down, start, pressurize or exhaust smoke during a fire event, bring AS 1668.1 into the review.
5Could moisture or maintenance affect hygiene?Where water, wet surfaces, condensate, cooling towers or cleaning access matter, investigate AS/NZS 3666.1 and 3666.2.
6Document the interfacesA final engineering basis should show how normal ventilation, fire mode, microbial control, maintenance and building approval requirements fit together.
The most common failure is a broken chain of assumptions.

A good result needs the equipment definition, loads, design method, fabrication, inspection and operating limits to describe the same real system.

05

Key engineering concepts to understand

01

Ventilation is not the same as comfort

A system can meet a ventilation objective and still have temperature, humidity, noise or air-movement complaints. Keep the engineering question clear.

02

The same AHU can have several jobs

Normal ventilation, smoke-control operation, shutdown logic and microbial-control design can all apply to one air-handling system.

03

Occupancy change can change the basis

A room that once worked acceptably may need reassessment when density, use, operating hours or contaminant generation changes.

04

Natural ventilation is an engineered pathway

Openable windows, roller doors and louvres only help when the required opening geometry and operating assumptions are actually available.

05

Maintenance access begins at design

Filters, coils, drains, humidifiers and wet components cannot be maintained well if the original design makes them inaccessible.

06

Measurements need context

CO2, airflow, pressure and contaminant readings are evidence. They become useful only when connected to occupancy, system operation, outdoor conditions and the relevant design basis.

06

Detailed engineering case studies

The examples below show how the Standard changes a real engineering decision. They are not clause summaries or universal answers; each case starts with the equipment, task and evidence available.

Case study 1 · Existing office fit-out

Meeting room converted into a high-occupancy training room

01
Project context

An office meeting room that previously held eight people is reconfigured for twenty-five-person training sessions. Complaints of stuffiness begin, and portable CO2 monitors show rising concentrations during long sessions.

Why this Standard matters

The first question is mechanical ventilation under AS 1668.2, but the assessment also needs the actual occupancy, room use, air distribution and system operating schedule. A CO2 reading by itself is not the design calculation.

What made the job difficult

  • The original design documentation lists the old room use but not measured supply or outdoor-air quantities.
  • The VAV box may reduce airflow when sensible cooling demand is low even though the room is fully occupied.
  • The room door is often closed for acoustic reasons and sessions last several hours.
  • The central AHU serves many spaces, so increasing one room’s demand can affect the wider system balance.

How the engineering review should proceed

  1. Confirm the actual occupancy pattern and intended room classification before selecting the ventilation basis.
  2. Review the air path from outdoor-air intake through the AHU and terminal system to the room, including operating schedules and control sequences.
  3. Measure relevant airflow and trend CO2 as supporting evidence, but interpret the data against occupancy and outdoor concentration.
  4. Check whether changes are needed at room, terminal, AHU or controls level rather than simply opening the outdoor-air damper further.
Practical outcome

A strong outcome is a documented ventilation adequacy assessment that identifies the changed occupancy as the trigger, verifies the existing system capacity and defines balancing or control changes. The conclusion should not be ‘CO2 was high, therefore non-compliant’ without the system evidence.

Also investigate
AS 1668.2BMS trend dataCommissioning and balancingThermal comfort as a separate issue
Case study 2 · Mixed ventilation strategy

Warehouse relies on louvres, roller doors and local exhaust fans

02
Project context

A warehouse has permanent wall louvres, large roller doors that are usually open during the day and several local exhaust fans. A refurbishment encloses part of the building and adds racking near the louvres.

Why this Standard matters

This is not a simple ‘natural or mechanical’ binary. The review needs to identify which spaces rely on AS 1668.4, which depend on mechanical exhaust under AS 1668.2 and whether the refurbishment blocks the original air path.

What made the job difficult

  • Roller doors are operational openings and may not be a reliable permanent ventilation assumption.
  • New internal partitions create deeper zones with weaker natural air paths.
  • Racking and stored goods partly obstruct existing louvres.
  • Local exhaust fans require a dependable source of make-up air.

How the engineering review should proceed

  1. Map each enclosure and identify the intended ventilation method rather than assessing the building as one large volume.
  2. Separate permanent natural openings from openings that depend on operator behaviour.
  3. Check how obstructions, adjacent buildings and internal partitions affect the opening arrangement and cross-ventilation path.
  4. Review mechanical exhaust and make-up air together so extraction does not create unintended pressure or performance problems.
Practical outcome

The likely result is a mixed ventilation basis: some zones remain naturally ventilated, while enclosed or process-affected areas require mechanical ventilation. The refurbishment should document the new air paths rather than inherit the original assumptions blindly.

Also investigate
AS 1668.4AS 1668.2NCC pathwayProcess-specific contaminant controls
Case study 3 · HVAC plant replacement

Replacing an old AHU in a multi-storey commercial building

03
Project context

An ageing air-handling unit is to be replaced with a modern high-efficiency unit. The new selection can meet normal supply-air duty, but the original documentation shows that the system also participates in fire-mode operation.

Why this Standard matters

The replacement cannot be reviewed only as an energy or comfort upgrade. AS 1668.1 fire-mode functions, AS 1668.2 ventilation performance and AS/NZS 3666 maintainability all intersect at the same piece of plant.

What made the job difficult

  • The new fan has a different drive and control architecture.
  • Existing dampers and fire-mode sequences are poorly documented.
  • The plantroom layout provides limited access to filters, coils and drains.
  • The owner wants to reuse existing controls to reduce shutdown time.

How the engineering review should proceed

  1. Separate the AHU requirements into normal mode, fire mode, shutdown/override logic and maintenance/hygiene functions.
  2. Recover the fire matrix, damper schedule and control interfaces before final equipment selection.
  3. Confirm outdoor-air and ventilation duty under the current building use, not only the historical design.
  4. Use the replacement opportunity to correct access, drainage and cleaning limitations that would otherwise remain for the life of the new unit.
Practical outcome

The replacement becomes a coordinated building-services modification package, not a fan-for-fan swap. The deliverables should show normal operation, fire-mode sequence, commissioning tests and maintainability of the new arrangement.

Also investigate
AS 1668.1AS 1668.2AS/NZS 3666.1Fire matrix and commissioning
07

Common mistakes

Saying ‘AS 1668 compliant’ without naming the part

The phrase hides whether the real issue is mechanical ventilation, natural ventilation or smoke control.

Treating CO2 as a pass/fail meter

A sensor reading is useful evidence but needs occupancy, outdoor concentration, airflow and operating context.

Ignoring the fire-mode role of normal HVAC equipment

An AHU or fan may appear ordinary in daily operation but have critical shutdown or smoke-control functions.

Assuming open doors count as permanent natural ventilation

Operational behaviour should not be substituted for a documented natural-ventilation basis.

Designing inaccessible plant

Poor access to coils, filters, drains and wet components undermines future maintenance and microbial control.

Fixing one room without checking system capacity

Increasing airflow in one zone can create balance, pressure or capacity problems elsewhere.

08

Information to gather before making the decision

Building classification and approval basis

Current space uses and occupant densities

Mechanical and fire-services drawings

Airflow schedules and commissioning records

BMS sequences and trend data

Outdoor-air intake and exhaust locations

Natural ventilation opening sizes and obstructions

Fire matrix and smoke-control sequence

AHU, fan, damper and control equipment data

Condensate, drainage and moisture history

Maintenance manuals and service records

Recent alterations, complaints and measured data

09

What should happen next?

1

Need mechanical ventilation guidance

Open the AS 1668.2 page and define the enclosure use, occupancy, contaminants and existing air path.

2

Relying on natural openings

Open the AS 1668.4 page and verify the permanent opening arrangement and NCC pathway.

3

Changing fans, dampers or AHUs

Check AS 1668.1 before assuming the equipment only serves normal HVAC operation.

4

Moisture or hygiene concerns

Use AS/NZS 3666.1 and 3666.2 to review design access, drainage, maintenance and records.

5

Existing building problem

Use the ventilation-assessment guide to combine drawings, measurements, operation and occupancy evidence.

Related AS Applied content

10

Source basis & limitations

  • This page is intentionally problem-led and does not reproduce ventilation-rate tables, smoke-control operating tables, figures or detailed formulae from the licensed Standards.
Project-specific engineering

Need the Standard applied to real equipment?

AS Applied helps frame the question. Detailed assessment, design, FEA, repair design, verification and RPEQ services are provided through XPO Engineers.

Ask an engineer